XGB Analog edition manual
(7) Scaling data type setting area (address 18)
(a) Scaling data type can set per channel.
(b) There are two type of scaling operation output, unsigned 16 bit (0~65535) or signed 16 bit (-
32768~32768).
(c) In case of using PUT instruction, scaling data type setting address is as follows.
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
Address “0”
—
—
—
—
—
—
—
—
—
—
—
—
C
H
3
C
H
2
C
H
1
C
H
0
Bit
Description
0
Signed integer
1
Unsigned integer
(d) Values set in B4~15 are ignored.
(e) This area shows the same results with Scaling data type setting in I/O parameter setting
window.
(8) Scaling min./max. value setting area (Address 19~26)
(a) Scaling min./max. value can be set per channel.
(b) There are two type of scaling operation output, unsigned 16 bit (0~65535) or signed 16 bit
(-32768~32767).
(c) In case of using PUT instruction, scaling min./max. value setting address is as follows.
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
Address “19”
CH# scaling min./max. value
1) with sign Min.: -32768 ~ [Scaling max. value-1]
Max.: [Scaling min. value+1]~32767
2) without sign Min.: 0 ~ [Scaling max. value-1]
Max.: [Scaling min.value+1]~65535
CH0: min. address 19 / max. address 20
CH1: min. address 21 / max. address 22
CH2: min. address 23 / max. address 24
CH3: min. address 25 / max. address 26
Address “20”
Address “21”
Address “22”
Address “23”
Address “24”
Address “25”
Address “26”
(d) If input is out of range, it keeps previous value.
But, U0x.01.8~ U0x.01.B
(setting error representation, in case of IEC
type, %UX0.x.24~%UX0.x.27) are on, error information is displayed at bit 6 of address 27~30.
5 - 48
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...