Chapter 2 Analog Input Module (XBF-AD04A)
2 - 11
(2) Filter processing
Filter process function is used to obtain stable digital output value by filtering (delaying) noise or
sudden change of input value. Filter constant can be specified for respective channels through user
program or I/O parameters setting.
•
Setting range: 1 ~ 99 (%)
F[n] = (1 -
α
) x A[n] +
α
x F [n - 1]
F[n]: Present filter output value
A[n]: Present A/D converted value
F[n-1]: Previous filter output value
Α
: Filter constant (0.01 ~ 0.99: previous value added)
If filter setting value is not specified within 1 ~ 99, RUN LED flickering at an interval of 1 second.
In order to set RUN LED to On status, reset the filter setting value within 1 ~ 99 and then
convert PLC CPU from STOP to RUN. Be sure to use request flag of error clear (UXY.11.0) to
clear the error through modification during RUN.
•
Analog input range: DC 0 ~ 10 V, Digital output range: 0 ~ 4000
•
If analog input value changes 0 V
10 V (0
4000), filter output value based on
value is
as specified below.
value
Filter output value
value
1 scan
2 scan
3 scan
*1)
0.01
0
3600
3960
3997
1% inclined toward previous value
*2)
0.66
0
1360
2257
2850
50% inclined toward previous value
*3)
0.99
0
40
80
119
99% inclined toward previous value
*1) 4000 output after about 4 scans
*2) 4000 output after about 18 scans
*3) 4000 output after about 950 scans(1.19 s for 1 channel Run)
If filter process function is not used, present A/D converted value will be output as it is. The filter
process function takes value-added data between ‘Present A/D converted value’ and ‘Previous
A/D converted value’. And the value-added data can be decided with filter constant. If output
data shakes too much, set a big filter constant value.
(3) Average processing
This process is used to execute A/D conversion of the channel designated for specified frequency or
for specified time and save the average of the accumulated sum on memory. Average processing
option and time/frequency value can be defined through user program or I/O parameters setting for
respective channels.
(a) What is the average process used for
This process is used for A/D conversion of abnormal analog input signal such as noise to a value
near to normal analog input signal.
(b) Average processing type
Average processing type is of time average and count average.
1) Time average processing
▪
Setting range: 4 ~ 16000 (ms)
▪
Average processing count within specified time is decided based on the number of channels
used.
Speed)
Conversion
(
x
used)
Channels
of
(Number
time
Setting
count
processing
Average
0 scan
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...