XGB Analog edition manual
5.2.6 Accuracy / Resolution
Accuracy / Resolution are as follows according to ambient temperature
Thermocouple
type
Measurement
temperature
range
Indication temperature
range
Accuracy
- note1)
resolution
Normal
temperature
(25
℃
)
Operating
temperature
-
note2)
(0
℃
~ 55
℃
)
K
-200.0
℃
~
1300.0
℃
-270.0
℃
~ -200.0
℃
- note3)
-200.0
℃
~ 0.0
℃
±3.0
℃
±7.5
℃
0.2
℃
0.0
℃
~ 1300.0
℃
±3.0
℃
±7.5
℃
0.1
℃
1300.0
℃
~ 1372.0
℃
- note3)
J
-200.0
℃
~
1200.0
℃
-210.0
℃
~ -200.0
℃
- note3)
-200.0
℃
~ -100.0
℃
±2.8
℃
±7.0
℃
0.2
℃
-100.0
℃
~ 1200.0
℃
±2.8
℃
±7.0
℃
0.1
℃
T
-200.0
℃
~
400.0
℃
-270.0
℃
~ -200.0
℃
- note3)
-200.0
℃
~ 400.0
℃
±1.2
℃
±3.0
℃
0.1
℃
R
0.0
℃
~
1700.0
℃
-50.0
℃
~ 0.0
℃
- note3)
0.0
℃
~ 1700.0
℃
±3.5
℃
±8.5
℃
0.5
℃
1700.0
℃
~ 1768.0
℃
- note3)
Note1) Total accuracy (normal temp.) = accuracy (normal temp.) + cold junction compensation accuracy
= ±(full scale X 0.2% + 1.0
℃
)
Cold junction compensation accuracy = ±1.0
℃
Note2) Temp. coefficient: ±100 ppm/
℃
Note3) Measuring the temp. is available, but accuracy and resolution is not guaranteed.
(1) When ambient temp. is normal (25 ± 5
℃
): within the ±0.2% range of measurement temp.
(2) When ambient temp. is operating temp. (0 ~ 55
℃
): within the ±0.5% range of measurement temp.
Ex.) When K type thermocouple is used and ambient temperature is normal.
In case of measuring 1000
℃
temperature, output range of conversion data is
1000
℃
- [{1300 - (-200)} x 0.2 %] - 1 ~ 1000
℃
+ [{1300 - (-200)} x 0.2 %] + 1
namely, 996.0 ~ 1004.0 [
℃
].
(1) For stabilization of measurement temperature, warming-up time more than 15 min. is necessary, after
restart.
(2) If ambient temperature changes rapidly, measurement temperature may change temporally. Keep the
ambient temperature steady for stabilization of measuring temperature.
(3) If wind of the cooling pan contacts with module directly in the panel, accuracy decreases. Do not
contact with wind directly.
Note
5 - 12
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...