XGB Analog edition manual
15 - 12
(c) Input items
The items to set in the built-in PID function parameter window and the available scope
of them are summarized in below table.
Items
Description
Scope
RUN mode
Set the operation mode of PID control.
Auto/manual
operation
RUN direction
Set the operation direction of PID control.
Forward/reverse
Prevention of dual
integral accumulation
Set whether to allow dual integral accumulation.
Disabled/enabled
PWM output
Set whether to allow PWM output of maneuver
value.
Disabled/enabled
Operation cycle time
Set the operation cycle time of PID control
cycle.
100 ~ 65535
Set value
Set target control value.
-32,768 ~ 32,767
Proportional gain
Set proportional gain.
Real number
Integral time
Set integral time.
Real number
Differential time
Set differential time.
Real number
Limiting change of
present value
Set the limited change of present value per
operation cycle.
-32,768 ~ 32,767
Limiting change of
maneuver value
Set the limited change of maneuver value per
operation cycle.
-32,768 ~ 32,767
Max. maneuver value
Set the max. maneuver value for control.
-32,768 ~ 32,767
Min. maneuver value
Set the min. maneuver value for control.
-32,768 ~ 32,767
Manual maneuver
value
Set the manual maneuver value for control.
-32,768 ~ 32,767
DeadBand setting
Set the deadband width of the set value.
0 ~ 65,535
Differential filter value
Set the filter coefficient of differential operation.
0 ~ 65,535
PWM junction
Set the junction to which PWM output is out.
P20 ~ P3F
(%QX0.0.0~%QX0.0.31)
PWM output cycle
Set the output cycle of PWM output.
100 ~ 65,535
Set value ramp
Set the frequency of set value ramp.
0 ~ 65,535
Present value follow-
up
Set the follow-up frequency of the present value
follow-up function.
0 ~ 65,535
Min. present value
Set the min. value of the input present value.
-32,768 ~ 32,767
Max. present value
Set the max. value of input present value.
-32,768 ~ 32,767
< Table 15.7 PID function parameter setting items >
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...