Chapter 8 Analog Input Option Board (XBO-AD02A)
(1) Module Ready/Error Flag ( ( ) is for IEC types, y: slot No.)
(a) U0y.00.F(%UX0.y.15)
:
at power on or reset of PLC CPU, turns on when the analog I/O
conversion is ready and analog conversion is performed.
(b) U0y.00.0(%UX0.y.0)
:
the flag indicating the error status of analog input option board module.
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
-
-
-
-
-
-
-
-
-
-
-
U0
y
.00
(%
UW0.
y
.0)
Error occurrence
information
Bit On (1): error
Bit Off (0): Normal
Rea
dy
Error
-
-
-
Module READY
Bit On (1): Normal
Bit Off (0): error
(2) Operation channel information/ channel error information flag ( ( ) is for IEC types, y: slot No.)
This is the area for storing the operation information and channel error information by channel.
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
-
-
In
p
u
t
C
H
1
In
p
u
t
C
H
0
-
-
-
-
-
-
U0
y
.01
(%
UW0.
y
.1)
Operating CH
information
Bit On (1): operating
Bit Off (0): stop
In
p
u
t
C
H
1
In
p
u
t
C
H
0
-
-
In
p
u
t
C
H
1
In
p
u
t
C
H
0
CH error information
Bit On (1): error
Bit Off (0): normal
CH disconnection
information
Bit On (1): disconnection
Bit Off (0): normal
(3) Digital Output Values ( ( ) is for IEC types, y: slot No.)
(a) A/D converted digital values are outputted to buffer memory address U0y.04 ~ U0y.05 by
channel-basis.
(b) Digital output values are saved in 16-bit binary figures.
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
Input CH0 conversion value
U0
y
.04
(%
UW0.
y
.4)
Input CH1 conversion value
U0
y
.05
(%
UW0.
y
.5)
8 - 27
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...