Chapter 2 Analog Input Module (XBF-AD04A)
2 - 31
2.12.2 Operation parameters setting area
Setting area of A/D conversion module’s Run parameters is as described in Table.
Memory address
Details
R/W
Remark
Hex.
Dec.
0
H
0
Channel
enable/disable
setting
R/W
PUT
1
H
1
Setting ranges of input
voltage/current
R/W PUT
2
H
2
Output data format setting
R/W
PUT
3
H
3
Filter processing enable/disable
setting
R/W PUT
4
H
4
CH0 filter constant
R/W PUT
5
H
5
CH1 filter constant
6
H
6
CH2 filter constant
7
H
7
CH3 filter constant
C
H
12
Average processing enable/disable
setting
R/W
PUT
D
H
13
Average processing method setting
R/W
E
H
14
CH0 average value
R/W
F
H
15
CH1 average value
10
H
16
CH2 average value
11
H
17
CH3 average value
16
H
22
Error
code
R/W GET
※
R/W is to denote Read/Write if available from PLC program.
(1) Setting operation channels
If the channel to use is not specified, all the channels will be set to prohibit.
(2) Setting input range
The range of analog voltage input is DC 0~10V, the range of analog current input is DC 4~20mA.
bit15 bit14 bit13 bit12 bit11 bit10 bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1 bit0
—
—
—
—
—
—
—
—
—
—
—
—
CH.
3
CH.
2
CH.
1
CH.
0
bit15 bit14 bit13 bit12 bit11 bit10 bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1 bit0
—
—
—
—
—
—
—
—
CH.3
CH.2
CH.1
CH.0
Setting channel to use (bit)
Bit On (1): Run, Bit Off (0): Stop
Address 0
Setting input range (bit)
00: 0 ~ 10V(4 ~ 20mA)
01: 0 ~ 20mA
11: 4 ~ 20mA
Address 1
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...