XGB Analog edition manual
15 - 24
11) _PIDxx_MV (Control MV)
The area shows the MV of
‘xx’ th PID control loop. As the area in which XGB built-in PID
operation result is output every PID control cycle, it delivers the value in the area to U device
every scanning by using commands like MOV in the program and outputs to D/A output module,
operating a drive.
12) _PID00_ERR (Present error)
T
he areas shows the current error of
‘xx’ th PID control loop. It is also used as an indicator about
how much gap the present status has with a desired status and if an error is 0, it means the
control system reaches a desired status exactly. Therefore, if control starts, error is quickly
reduced at transient state and it reaches normal state, maintaining remaining drift as 0, it could
be an ideal control system. The flag, as a dedicated monitoring, is updated although a user
directly enters it.
13) _PIDxx_MV_p, _PIDxx_MV_i, _PIDxx_MV_d (P/I/D control components of MV)
It indicates
‘n’ th loop MV by classifying proportional control MV, integral control max. MV and
differential control MV. The entire MV consists of the sum of these three components. The flag,
as a dedicated monitoring, is updated although a user directly enters it.
14) _PIDxx_DB_W (DeadBand setting)
It sets the deadband of
‘xx’ th loop. For more information about Deadband function, refer to
15.2.3 PID control parameter setting. If it is set as 0, the function does not work.
15) _PIDxx_Td_lag (Differential filter coefficient)
It sets the differential filter coefficient of
‘xx’ th loop. For more information about differential filter
coefficient, refer to 15.2.3 PID control parameter setting. If it is set as 0, the function does not
work.
Flag name
Address
IEC type address
Unit
Scope
_PIDxx_MV (control MV)
K1231+16*xx
%16*xx
INT
Unavailable
Flag name
Address
IEC type address
Unit
Scope
_PID00_ERR
(present error)
K1232+16*xx %16*xx
DINT
Unavailable
Flag name
Address
IEC type address
Unit
Scope
_PIDxx_MV_p
(MV proportional control component)
K1234+16*xx
%KD616+20*xx
REAL
Unavailable
_PIDxx_MV_i
(MV integral control component)
K1236+16*xx %KD617+20*xx
_PIDxx_MV_d
(MV differential control component)
K1238+16*xx %KD618+20*xx
Flag name
Address
IEC type address
Unit
Scope
_PIDxx_DB_W
(DeadBand setting)
K1240+16*xx %16*xx WORD
0 ~ 65,535
Flag name
Address
IEC type address
Unit
Scope
_PIDxx_Td_lag
(differential filter coefficient)
K1241+16*xx
%16*xx
WORD
0 ~ 65,535
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...