Chapter 5 Thermocouple Input Module (XBF-TC04S,TC04B)
(e) This area shows the same results with Scaling min./max. value setting in I/O parameter setting
window.
Scaling data
type
Scaling min. value
Scaling max. value
Signed
-32768 ~ [Scaling max. value -1]
[Scaling min. value+1] ~ 32767
Unsigned
0 ~ [Scaling max. value-1]
[Scaling min. value+1] ~ 65535
(9) Setting error information area (address 27~30)
(a) If there is error when setting parameter (address 1~26), error information is displayed at
address 27~30 per channel.
(b) In case of GET instruction, setting error information address is as follows.
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
Address “27”
CH0 setting error information
Address “28”
CH1 setting error information
Address “29”
CH2 setting error information
Address “30”
CH3 setting error information
Bit
Description
Related memory
address
Hex.
Dec.
Bit0
Sensor type (Off: normal, On: error)
01
H
~04
H
1~4
Bit1
Filter constant (Off: normal, On: error)
06
H
~09
H
6~9
Bit2
Average processing method
(Off: normal, On: error)
0A
H
~0D
H
10~13
Bit3
Time-average value (Off: normal, On: error)
0E
H
~11
H
14~17
Bit4
Count-average value (Off: normal, On: error))
Bit5
Moving-average value (Off: normal, On: error)
Bit6
Scaling range (Off: normal, On: error)
13
H
~1A
H
19~26
(c) In case there is error, setting error representation flag (U0x.01.8 ~ U0x.01.B, in case of IEC
type, %UX0.x.24 ~ %UX0.x.27) will be on, it acts as default value.
If setting error representation flag (U0x.01.8 ~ U0x.01.B) is on, check error information 1B
H
~
1F
H
(27~30) area and solve the error.
5 - 49
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...