Code and
Features
Description
End
[Acceleration / deceleration pattern configuration]
[Acceleration / deceleration S-curve pattern configuration]
Note
The Actual Acc/Dec time during an S-curve application
Actual acceleration time = user-configured acceleration time + user-configured
acceleration time x starting gradient level/2 + user-configured acceleration time x ending
gradient level/2.
Actual deceleration time = user-configured deceleration time + user-configured
deceleration time x starting gradient level/2 + user-configured deceleration time x ending
gradient level/2.