![LSIS G100 Operation Manual Download Page 242](http://html.mh-extra.com/html/lsis/g100/g100_operation-manual_1944296242.webp)
Comm.
Address
Parameter
Scale Unit R/W
Assigned Content by Bit
0h0009
Output current
0.1
A
R
-
0h000A
Output frequency
0.01
Hz
R
-
0h000B
Output voltage
1
V
R
-
0h000C
DC link voltage
1
V
R
-
0h000D
Output power
0.1
kW
R
-
0h000E
Operation status
-
-
-
B15
Reserved
B14
1: Frequency command
source by
communication (built-in,
option)
B13
1: Operation command
source by
communication (built-in,
option)
B12
Reverse operation
command
B11
Forward operation
command
B10
Brake release signal
B9
Jog mode
B8
Drive stopped.
B7
DC Braking
B6
Speed reached
B5
Decelerating
B4
Accelerating
B3
Fault Trip - operates
according to OU.30
setting
B2
Operating in reverse
direction
B1
Operating in forward
direction
B0
Stopped
0h000F
Fault trip information
-
-
R
B15
Reserved
B14
Reserved
B13
Reserved
B12
Reserved
B11
Reserved
B10
H/W-Diag
B9
Reserved
B8
Reserved
B7
Reserved
B6
Reserved
B5
Reserved
B4
Reserved
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...