3.3.3 Jog Frequency Configuration
The following example demonstrates how to configure Jog Frequency by modifying
code 11 (Jog Frequency) in the Drive group from 10.00 Hz to 20.00 Hz. You can
configure the parameters for different codes in any other group in exactly the same
way.
Step
Instruction
Keypad Display
1
Go to code 11 (dr.11) in the Drive group.
2
Press the [ENT] key.
The current Jog Frequency value (10.00) for code dr.11 is
displayed.
3
Press the [MODE] key 3 times to move to the tens' place
value.
"1" in the tens' place will flash.
4
To make the target value "20.00", press the [
▲] key to
change the tens' place value to "2", and then press the
[ENT] key.
The selected value will flash on the display.
5
Press the [ENT] key again to save the changes.
Code dr.11 will be displayed. The parameter change has
been completed.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...