Group Code
Name
Setting
Setting Range
Unit
voltage (%)
14
V1 Maximum input
voltage
-10.00
-12.00
–0.00 V
V
15
V1 output at Maximum
voltage (%)
-100.00
-100.00
–0.00%
%
Rotational Directions for Different Voltage Inputs
Operation
command
Input voltage
0
–10 V
-10
–0 V
FWD
Fwd
Rev
REV
Rev
Fwd
-10
–10 V Voltage Input Setting Details
Code and
Features
Description
In.12 V1
– volt
x1
–
In.15 V1
–
Perc
y2
Sets the gradient level and off-set value of the output frequency in
relation to the input voltage. These codes are displayed only when
In.06 is set to 1 (bipolar).
For example, if the ln.12 code is set to -2 V, In.13 code is set to 10%,
In.14 code is set to -8 V, and In.15 code is set to 80%, the output
frequency will vary within the range of 6
–48 Hz.
For details about the 0
–+10 V analog inputs, refer to the code
descriptions
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...