4.1.2 Set the Operation Frequency from the Keypad - Using [
▲]
and [
▼] keys
You can use the [
▲] and [▼] keys like a potentiometer to modify the frequency
reference. Select the Frq (Frequency reference source) code in the Operation group
to 1 (Keypad-2). This allows frequency reference values to be increased or decreased
when the [
▲] and [▼] keys are pressed from the Operation group 0.00 (target
frequency).
Group
Code
Name
Setting
Setting Range
Unit
Operation
Frq
Frequency
reference source
1
KeyPad-2
0
–8
-
0.00
Target
frequency
0.00
Min to Max Frq*
Hz
* You cannot set a frequency reference that exceeds the Max. Frequency, as
configured with dr.20.
4.1.3 V1 Terminal as the Source
You can set the frequency by inputting the voltage from the V1 terminal (frequency
setting voltage terminal) from the control terminal block. Use voltage inputs ranging
from 0 to 10 V (unipolar) for forward only operation. Use voltage inputs ranging from -
10 to +10 V (bipolar) for both directions, where negative voltage inputs are used
reverse operations.
4.1.3.1 Setting a Frequency Reference for 0
–10 V Input
Set the Frq (Frequency reference source) code in the Operation group to 2 (V1), and
then set code 06 (V1 Polarity) to 0 (unipolar) in the Input Terminal group (IN). Use the
voltage output of the external controller or use the VR terminal (frequency setting
power terminal) of the control terminal to input voltage in the V1 terminal as the
volume resistance.
[Connecting to external power source]
[Connecting to internal power source]
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...