![LSIS G100 Operation Manual Download Page 286](http://html.mh-extra.com/html/lsis/g100/g100_operation-manual_1944296286.webp)
Code
Comm.
Address
Name
Setting
Range
Initial Value
Pro
pert
y*
V/
F
S
L
Ref.
monitor
AP-18
0h1812
PID feedback
monitor
(%)
0.00
-
O O
AP-19
0h1813
PID reference
setting
-100.00
–
100.00 (%)
50.00
O
O O
AP-20
0h1814
PID reference
source
0
Keypad
0:
Keypad
X
O O
1
V1
3
V0
4
I2
5
Int 485
7
FieldBus
AP-21
0h1815
PID feedback
source
0
V1
0: V1
X
O O
2
V0
3
I2
4
Int 485
6
FieldBus
AP-22
0h1816
PID controller
proportional
gain
0.0
–1000.0
(%)
50.0
O
O O
AP-23
0h1817
PID controller
integral time
0.0
–200.0
(s)
10.0
O
O O
AP-24
0h1818
PID controller
differentiation
time
0
–1000 (ms) 0
O
O O
AP-25
0h1819
PID controller
feed-forward
compensation
gain
0.0
–1000.0
(%)
0.0
O
O O
AP-26
Proportional
gain scale
0.0
–100.0
(%)
100.0
X
O O
AP-27
0h181B
PID output
filter
0
–10000
(ms)
0
O
O O
AP-28
0h181C PID Mode
0
Process
PID
0
X
O O
-
1
Normal
PID
AP-29
0h181D
PID upper limit
frequency
PID lower
limit
frequency
–
300.00 (Hz)
60.00
O
O O
AP-30
0h181E
PID lower limit
frequency
-300.00
–
PID upper
limit
frequency(H
-60.00
O
O O
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...