Under Torque Detection Action
The over and under torque detection level set as OU68, 71 parameters are set as the
ratio on motor's rated current.
Torque Detection Operation Setting Details
Code and
Features
Description
OU67, 70 Torque
detection
operation setting
0: None
Torque detection is not operating.
1: OT CmdSpd Warn
Detects over torque and outputs warning only
when the inverter output frequency is the same as the command
frequency.
2: OT Warning
Detects over torque during the operation and outputs
warning.
3: OT CmdSpdTrip
Detects over torque and generates a trip only
when the inverter output frequency is the same as the command
frequency.
4: OT Trip
Detects over torque during operation and generates a trip.
5: UT CmdSpd Warn
Detects under torque and outputs warning only
when the inverter output frequency is the same as the command
frequency.
6: OT Warning
Detects under torque during the operation and
outputs warning.
7: UT CmdSpd Trip
Detects under torque and generates a trip only
when the inverter output frequency is the same as the command
frequency.
8: UT Trip
Detects under torque during operation and generates a
trip.
OU.68, 71
Torque detection
level
Sets the torque detection level of torque detection 1, 2. The set value
is a% of the motor's rated current. The detection level must be higher
than Ba.14 no load current value.
OU.69, 72
Torque detection
Sets the delay time on torque detection 1, 2. When over or under
torque is detected, a warning or trip is output after the torque detection
OUT-68 or OUT-71
OUT-69 or OUT-72
Motor
Current
hysteresis(10%)
OUT-69 or OUT-72
MO
(42: Prt Trq Dect1
or 43: Prt Trq Dect2)
hysteresis(10%)
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...