Code and
Features
Description
Cn.70 SS Mode
Select a speed search type.
Configuration
Function
0
Flying Start-
1
The speed search is carried out as it controls
the inverter output current during idling
below the Cn.72 (SS Sup-Current)
parameter setting. If the direction of the
idling motor and the direction of operation
command at restart are the same, a stable
speed search function can be performed at
about 10 Hz or lower.
However, if the direction of the idling motor
and the direction of operation command at
restart are different, the speed search does
not produce a satisfactory result because the
direction of idling cannot be established.
1
Flying Start-
2
The speed search is carried out as it PI
controls the ripple current which is generated
by the counter electromotive force during no-
load rotation. Because this mode establishes
the direction of the idling motor
(forward/reverse), the speed search function
is stable regardless of the direction of the
idling motor and direction of operation
command. However because the ripple
current is used which is generated by the
counter electromotive force at idle (the
counter electromotive force is proportional to
the idle speed), the idle frequency is not
determined accurately and re-acceleration
may start from zero speed when the speed
search is performed for the idling motor at
low speed (about 10
–15 Hz, though it
depends on motor characteristics).
Cn.71 Speed
Search
Speed search can be selected from the following 4 options. If the top
display segment is on it is enabled (On), and if the bottom segment
is on it is disabled (Off).
Items
Bit On Status
Bit Off Status
Keypad
Type and Functions of Speed Search Setting
Configuration
Function
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...