11.5 Fuse and Reactor Specifications
Capacity (kW)
AC Input Fuse
AC Reactor
Model Current (A)
Voltage
(V)
Inductance (mH)
Current (A)
3-phase
200 V
0.4
DFJ-10
1)
10
600
1.20
10
0.75
1.5
DFJ-15
15
0.88
14
2.2
DFJ-20
20
0.56
20
4.0
DFJ-30
30
0.39
30
5.5
DFJ-50
50
0.30
34
7.5
DFJ-60
60
0.22
45
3-phase
400 V
0.4
DFJ-10
10
4.81
4.8
0.75
1.5
3.23
7.5
2.2
DFJ-15
15
2.34
10
4.0
DFJ-20
20
1.22
15
5.5
DFJ-30
30
1.12
19
7.5
DFJ-35
35
0.78
27
Note
1
) DFJ is Class J/600 V level model name of the Bussmann company.
Use Class CC, G, J, L, R or T UL Listed Input Fuse and UL Listed Breaker Only. See the
table above For the Voltage and Current rating of the fuse and the breaker.
Utiliser UNIQUEMENT des fusibles d’entrée homologués de Classe CC, G, J, L, R ou T
UL et des disjoncteurs UL. Se reporter au tableau ci-dessus pour la tension et le courant
nominal des fusibless et des disjoncteurs.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...