Code and
Features
Description
OU.31 Relay1,
OU.33 Relay 2
Set multi-function output terminal or relay to be used as a timer to 28
(Timer out).
OU.55
TimerOn Delay,
OU.56
TimerOff Delay
Input a signal (On) to the timer terminal to operate a timer output (Timer
out) after the time set at OU.55 has passed. When the multi-function
input terminal is off, multi-function output or relay turns off after the time
set at OU.56.
5.25 Brake Control
This feature controls
the On/Off operation of the load’s electronic braking system.
Group Code
Name
Setting
Setting
Range
Unit
dr
09
Control mode
0
V/F
-
-
Ad
41
Brake release current
50.0
0.0
–180%
%
42
Brake release delay time
1.00
0.0
–10.0
sec
44
Brake release Forward
frequency
1.00
0
–Max
Frequency
Hz
45
Brake release Reverse
frequency
1.00
0
–Max
Frequency
Hz
46
Brake engage delay time
1.00
0.00
–10.00
sec
47
Brake engage frequency
2.00
0
–Max
Frequency
Hz
OU
31
Multi-function relay 1 item
35
BR
Control
:
-
-
33
Multi-function relay 2 item
When brake control is activated, DC braking (Ad.12) at inverter start and dwell
operation (Ad.20
–23) do not operate.
•
Brake release sequence:
During motor stop state, if an operation command is
entered, the inverter accelerates up to brake release frequency (Ad.44
– 45) in
forward or in reverse direction. After reaching brake release frequency, if motor
current reaches brake release current (BR Rls Curr), the output relay or multi-
function output terminal for brake control sends a release signal. Once the signal
has been sent, acceleration will begin after maintaining frequency for brake release
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...