Trip Setting Details to Multi-Function Relay
Code and
Features
Description
OU.30 Trip Out
Mode
Fault trip relay operates based on the fault trip output settings.
Items
Bit On Status
Bit Off Status
Keypad
After selecting the multi-function relay to use as the trip output,
select 29 (Trip Mode) in OU.31, 33. If the trip occurs from the
inverter, the applicable multi-function relay will be activated.
Activation status of multi-function relay can be set up as below
depending on the trip type.
Configuration
Function
bit3
bit2
bit1
Operates when low voltage fault trips
occur
Operates when fault trips other than low
voltage occur
Operates when auto restart fails (Pr. 08
–
09)
OU.31 Relay1
Set the Relay 1 output item.
OU.33 Relay 2
Set the Relay 2 output item.
OU.53 TripOut On
Dly, OU.54 TripOut
OffDly
If a trip occurs, multi-function relay 1 or multi-function relay 2 will be
activated after the time set in multi-function. Terminal is off with the
input initialized after the time delay set in OU.54.
5.29.3 Multi-Function Relay Terminal Delay Time Settings
Set On delay time and Off delay time specifically to adjust the multi-function relay
operation time of the terminal. The delay time set in OU.50
–51 will be applied to both
Relay 1 and Relay 2 except for when the multi-function relay feature is under trip
mode.
Group Code
Name
Setting
Setting
Range
Unit
OU
50
Multi-function output On
delay
0.00
0.00
–
100.00
sec
51
Multi-function output Off
delay
0.00
0.00
–
100.00
sec
52
Multi-function output
contact selection
00*
00
–11
bit
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...