1.5 Cable Selection
When you install power and signal cables in the terminal blocks, only use cables that
meet the required specification for the safe and reliable operation of the product.
Refer to the following information to assist you with cable selection.
•
Wherever possible use cables with the largest cross-sectional area for mains power
wiring, to ensure that voltage drop does not exceed 2%.
•
Use copper cables rated for 600 V, 75
℃
for power terminal wiring.
•
Use copper cables rated for 300 V, 75
℃
for control terminal wiring.
Ground Cable and Power Cable Specification
Capacity (kW)
Ground
Power Terminal Wiring
Terminal
Block Size
mm
2
AWG
mm
2
AWG
R/S/T
U/V/W
R/S/T
U/V/W
3
–Phase
200 V
0.4
4
12
1.5
1.5
16
16
M3
0.75
1.5
4
12
4
2.5
12
14
M4
2.2
4
6
10
6
6
10
10
M4
5.5
6
10
16
10
6
8
M4
7.5
3
–Phase
400 V
0.4
2.5
14
1.5
1.5
16
16
M3.5
0.75
1.5
2.2
4
6
10
2.5
2.5
14
14
M4
5.5
6
10
10
6
8
10
M4
7.5
Signal (Control) Cable Specifications
Terminals
Control Terminal Wiring
Without Crimp Terminal
Connectors
With Crimp Terminal
Connectors
mm
2
AWG
mm
2
AWG
24/P1,
P2
–P5,
CM
0.8
18
0.5
20
A1/B1/C1/A2/C2,
VR/V1/I2/AO/CM,
S+/S-
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...