Request
ENQ
Station ID
CMD
Data
SUM
EOT
1 byte
2 bytes
1 byte
n bytes
2 bytes
1 byte
Normal Response
ACK
Station ID
CMD
Data
SUM
EOT
1 byte
2 bytes
1 byte
n x 4 bytes
2 bytes
1 byte
Error Response
NAK
Station ID
CMD
Error Code
SUM
EOT
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
•
A request starts with ENQ and ends with EOT.
•
A normal response starts with ACK and ends with EOT.
•
An error response starts with NAK and ends with EOT.
•
A station ID indicates the inverter number and is displayed as a two-byte ASCII-
HEX string that uses characters 0
–9 and A–F. ASCII-HEX is a hexadecimal
notation composed of numbers between 0
–9 and letters between A–F.
•
CMD: Uses uppercase characters (returns an IF error if lowercase characters are
encountered)
—please refer to the following table.
Character
ASCII-HEX
Command
‘R’
52h
Read
‘W’
57h
Write
‘X’
58h
Request monitor registration
‘Y’
59h
Perform monitor registration
•
Data will be displayed as ASCII-HEX. (For example, if data value is 3000:
3000 →
‘0’’B’’B’’8’h → 30h 42h 42h 38h).
•
Error code: ASCII-HEX (refer to
•
Transmission/reception buffer size: Transmission=39 bytes, Reception=44 bytes
•
Monitor registration buffer: 8 Words
•
SUM: Checks communication errors via sum.
SUM=a total of the lower 8 bits values for station ID, command and error code
(Station ID+CMD+error code) in ASCII-HEX.
For example, a read request to read 1 address from address 3000 is
SUM=‘0’+‘1’+’R’+‘3’+‘0’+‘0’+‘0’+’1’ = 30h+31h+52h+33h+30h+30h+30h+31h = 1
A7h. When calculating SUM, the control value like ENQ, ACK, and NAK are not
included. Since SUM takes a lower byte, A7h becomes SUM.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...