3.3.4 Parameter Initialization
The following example demonstrates parameter initialization using code dr.93
(Parameter Initialization) in the Drive group.
Step
Instruction
Keypad Display
1
Go to code 0 in the Drive group.
2
Press the [ENT] key.
The current parameter value "9" will be displayed.
3
To make the target value "93", press the [
▼] key to
change the ones' place value to "3".
4
Press the [MODE] key to move to the tens' place value.
5
To make the target value "93", press the [
▲] or [▼] key
to change the tens' place value "9".
6
Press the [ENT] key.
Code dr.93 will be displayed.
7
Press the [ENT] key once again.
The current parameter value for code dr.93 is set to 0
(Do not initialize).
8
Press the [▲] key to change the value to 1 (All Grp), and
then press the [ENT] key.
The parameter value will flash.
9
Press the [ENT] key once again.
Parameter initialization begins. Parameter initialization is
complete when code dr.93 reappears on the display.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...