Auto-Tuning Default Settings
Motor
Capacity
(kW)
Rated
Current (A)
No-load
Current
(A)
Rated Slip
Frequency
(Rpm)
Stator
Resistance
(
)
Leakage
Inductance
(mH)
200 V
0.2
1.1
0.8
100
14.0
40.4
0.4
1.9
1.0
90
6.42
38.8
0.75
3.3
1.7
70
2.951
25.20
1.5
5.9
2.7
70
1.156
12.07
2.2
8.6
3.9
50
0.809
6.44
3.7
13.8
5.7
50
0.485
4.02
5.5
20.0
6.2
50
0.283
3.24
7.5
25.5
7.4
50
0.183
2.523
400 V
0.2
0.7
0.5
100
28.00
121.2
0.4
1.1
0.6
90
19.40
117.0
0.75
1.9
0.9
70
8.97
76.3
1.5
3.4
1.7
70
3.51
37.3
2.2
4.3
2.3
50
3.069
24.92
3.7
6.9
3.2
50
1.820
15.36
5.5
11.5
3.6
50
0.819
9.77
7.5
15.0
4.4
50
0.526
7.58
Auto Tuning Parameter Setting Details
Code and
Features
Description
bA.20 Auto
Tuning
Select an auto tuning type and run it. Select one of the options and
then press the [ENT] key to run the auto tuning.
Configuration
Function
0
None
Auto tuning function is not enabled. If the auto
tuning function is ran, this will indicate that the
auto tuning is complete.
1
All
(Rotation
type)
Measures all motor parameters, including stator
resistance (Rs), leakage inductance (Lsigma),
stator inductance (Ls), no-load current (Noload
Curr), and rotor time constant (Tr) while the
motor is rotating.
As the motor is rotating while the parameters are
being measured, if the load is connected to the
motor spindle, the parameters may not be
measured accurately. For accurate
measurements, remove the load attached to the
motor spindle. However, note that the rotor time
constant (Tr) must be measured in a stopped
position.
2
All (static
Measures all parameters while the motor is in the
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...