Fire mode operation may result in inverter malfunction. Note that if AD 83 Fire mode count
is not "0m" the warranty is voided.
Code
Description
Details
Ad.81
Fire
Mode
frequency
Fire mode
frequency
reference
The frequency set at Ad. 81 (Fire mode frequency) is used
for the inverter operation in Fire mode. The Fire mode
frequency takes priority over the Jog frequency, Multi-step
frequencies, and the keypad input frequency.
Dr.03 Acc
Time /
Dr.04
Dec Time
Fire mode
Acc/Dec times
During Fire Mode operation, the inverter accelerates for
the time set in Dr 03. Acc Time. If the Px terminal input set
as Fire Mode input becomes Off status, the inverter
decelerates for the time set in Dr 0.4. Dec Time until the
operation is ended.
PR.10
Retry
Delay
Fault trip process
Some fault trips are ignored during Fire mode operation.
The fault trip history is saved, but trip outputs are disabled
even when they are configured at the multi-function output
terminals.
Fault trips that are ignored in Fire mode
BX, External Trip, Low Voltage Trip, Inverter Overheat,
Inverter Overload, Overload, Electrical Thermal Trip,
Input/Output Open Phase, Motor Overload, Fan Trip, No
Motor Trips, and other minor fault trips.
For the following fault trips, the inverter performs a Reset
and Restart until the trip conditions are released. The retry
delay time set at PR. 10 (Retry Delay) applies while the
inverter performs a Reset and Restart.
Fault trips that force a Reset Restart in Fire mode
Over Voltage, Over Current1 (OC1), Ground Fault Trip
The inverter stops operating when the following fault trips
occur:
Fault trips that stop inverter operation in Fire mode
H/W Diag, Over Current 2 (Arm-Short)
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...