Code and
Features
Description
Pr.79 FAN
Trip Mode
Set the cooling fan fault mode.
Configuration
Function
0
Trip
The inverter output is blocked and the fan trip
is displayed when a cooling fan error is
detected.
1
Warning
When OU.33 (Relay 2) and OU.31 (Relay 1)
are set to 8 (FAN Warning), the fan error signal
is output and the operation continues.
OU.31 Relay 1,
OU.33 Relay 2
When the code value is set to 8 (FAN Warning), the fan error signal
is output and operation continues. However, when the inverter inside
temperature rises above a certain level, output is blocked due to
activation of overheat protection.
6.3.2 Lifetime Diagnosis of Components
Lifetime Diagnosis for Fans
Enter the Pr-87 (Fan exchange warning level) code (%). After the selected usage (%)
is reached (out of 50,000 hours), the fan exchange warning message will appear in
the multi-functional output or keypad.
The total fan usage level (%) appears at Pr-86. When exchanging fans, you may
initialize the accumulated value to 0 by setting the Pr-88 (Initializing accumulated time
for cooling fans) to 1.
Group Cod
e
Name
Setting
Setting Range
Unit
Pr
86
Accumulated percent of
fan usage
0.0
0.0
–6553.5
%
87
Fan exchange warning
Level
90.0
0.0
–100.0
%
OU
31
Multi-function relay 1
item
37 FAN Exchange
-
-
33
Multi-function relay 2
item
6.3.3 Low Voltage Fault Trip
When inverter input power is lost and the internal DC link voltage drops below a
certain voltage level, the inverter stops output and a low voltage trip occurs.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...