6.1.2 Overload Early Warning and Trip
A warning or fault ‘trip’ (cutoff) occurs when the motor reaches an overload state,
based on the
motor’s rated current. The amount of current for warnings and trips can
be set separately.
Group Code
Name
Setting
Setting
Range
Unit
Pr
04
Load level setting
1
Heavy Duty
-
-
17
Overload warning
selection
1
Yes
0
–1
-
18
Overload warning level 150
30
–180
%
19
Overload warning time 10.0
0
–30
sec
20
Motion at overload fault 1
Free-Run
-
-
21
Overload fault level
180
30
–200
%
22
Overload fault time
60.0
0
–60.0
sec
OU
31
Multi-function relay 1
item
5
Over Load
-
-
33
Multi-function relay 2
item
Overload Early Warning and Trip Setting Details
Code and
Features
Description
Pr.04 Load Duty
Select the load level.
Configuration
Function
0
Normal
Duty
Used in underloads, like fans and pumps
(overload tolerance: 120% of rated underload
current for 1 minute).
1
Heavy
Duty
Used in heavy loads, like hoists, cranes, and
parking devices (overload tolerance: 150% of
rated heavy load current for 1 minute).
Pr.17 OL Warn
Select
If the overload reaches the warning level, the terminal block multi-
function output terminal and relay are used to output a warning
signal. If 1 (Yes) is selected, it will operate. If 0 (No) is selected, it
will not operate.
Pr.18 OL Warn
Level,
Pr.19 OL Warn
Time
When the input current to the motor is greater than the overload
warning level (OL Warn Level) and continues at that level during the
overload warning time (OL Warn Time), the multi-function output
(Relay 1, Relay 2) sends a warning signal. Multi-function relay
terminal and relay outputs signal if OU.31 and OU.33 codes are set
to 5 (Over load). The signal output does not block the inverter
output.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...