[Example of auto restart with a setting of 2]
If the auto restart number is set, be careful when the inverter resets from a fault trip. The
motor may automatically start to rotate.
5.15 Operational Noise Settings (Change of Carrier
Frequency Settings)
Group Code
Name
Setting Range
Unit
Cn
04
Carrier Frequency
0.4kW~4.0kW
2.0~15.0
kHz
5.5kW~7.5kW
1.0~15.0
* PWM: Pulse width modulation
Operational Noise Setting Details
Code and
Features
Description
Cn.04 Carrier
Freq
Adjust motor operational noise by changing carrier frequency settings.
Power transistors (IGBT) in the inverter generate and supply high
frequency switching voltage to the motor. The switching speed in this
process refers to the carrier frequency. If the carrier frequency is set
high, it reduces operational noise from the motor, and if the carrier
frequency is set low, it increases operational noise from the motor.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...