User V/F Pattern Setting Details
Code and
Features
Description
bA.41 User Freq
1
–
bA.48 User Volt
4
Select the arbitrary frequency between the start and the maximum
frequencies to set the user frequency (User Freq x). Also set the
voltage to correspond to each frequency in user voltage (User Volt x).
The 100% output voltage in the figure below is based on the parameter settings of
bA.15 (motor rated voltage). If bA.15 is set to 0 it will be based on the input voltage.
•
When a normal induction motor is in use, care must be taken not to configure the
output pattern away from a linear V/F pattern. Non-linear V/F patterns may cause
insufficient motor torque or motor overheating due to over-excitation.
•
When a user V/F pattern is in use, forward torque boost (dr.16) and reverse torque
boost (dr.17) do not operate.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...