Chapter 7 Built-in High-speed Counter Function
XBC E-Type Main Unit
7-18
Ver. 1
5. Borrow signal
a. Borrow signal occurs
i. When count range minimum value of -2,147,483,648 is reached during Linear
Count.
ii. When user-defined minimum value of Ring Count changed to the maximum
value during Ring Count.
b. Count when Borrow signal occurs
i. Count stops if Borrow occurs during Linear Count.
ii. Count does not stop even if Borrow occurs during Ring Count.
c. Borrow reset
i. The Borrow generated can be cancelled by Carry/Borrow reset signal On.
Classification
Device area per channel
Channel 0
Channel 1
Channel 2
Channel 3
Borrow signal
K2611
K2711
K2811
K2911
6. Revolution/Unit time
While auxiliary mode enable signal is On, it counts the number of input pulses for a specified
time.
a. Setting
i. Input unit time and pulse number per 1 revolution
I.
Setting value is saved at the following special K are and user can
designate it directly.
Classification
Device area per channel
Channel 0
Channel 1
Channel 2
Channel 3
Unit time (1~60000
㎳
)
*3)
K322
K352
K382
K412
*3) If revolution per unit time is enabled and unit time value is other than 1~60000ms, error code ‘34’ occurs.