Chapter 7 Built-in High-speed Counter Function
XBC E-Type Main Unit
7-13
Ver. 1
iii. In order to make actual comparison enabled after compared output condition is
set, the compared enable signal must be On.
Classification
Area per channel
Operation
Ch. 0
Ch. 1
Ch. 2
Ch. 3
Count enable signal
K2600
K2700
K2800
K2900
0: disable, 1: enable
Compared enable signal
K2604
K2704
K2804
K2904
0: disable, 1: enable
I.
In order to make external output, the compared equivalent output signal
(P20~P27) must be set. If Compared output contact is Off, Compared
coincidence output signal (internal device) is only output.
Classification
Area per channel
Operation
Ch. 0
Ch. 1
Ch. 2
Ch. 3
Compared equivalent
output signal
K2612
K2712
K2812
K2912
0: Compared output not
equivalent
1: Compared output
equivalent
II. Compared output point (P40 ~ P43) setting