Chapter 3 Installation and Wiring
XBC E-Type Main Unit
3-33
Ver. 1
Input Specifications
Input point
8 point, 1 COM
Insulation method
Photo-coupler insulation
Rated input voltage
DC24V
Rated input current
4mA (point 0-3: 7mA)
Operation voltage range
DC20.4~28.8V (within ripple rate 5%)
On voltage / On current
DC19V or higher / 3mA or higher
Off voltage / Off current
DC6V or lower / 1mA or lower
Input resistance
About 5.6k
Ω (P00-P03: 2.7kΩ)
Response
time
Off
→
On
1/3/5/10/20/70/100ms (set by I/O parameter) default: 3ms
On
→
Off
Insulation
Voltage/Resistance
AC560Vrms / 3 cycle (altitude 2000m); 10M
Ω or higher
Output Specifications
Output point
8 point
Insulation method
Relay insulation
Rated load
voltage/current
DC24V 2A (resistive load) / AC220V 2A (COS
Φ
= 1), 5A/COM, 4 COM (Isolated)
Min. load voltage/current
DC5V / 1mA
Max. load voltage
AC250V, DC125V
Off leakage current
0.1mA (AC220V, 60Hz)
Max. On/Off frequency
3,600 times / hour
Surge absorber
None
Service life
Mechanical
20 million times or more
Electrical
Rated load voltage / Current 100,000 times or more
AC200V / 1.5A, AC240V / 1A (COS
Φ
= 0.7) 100,000 times or more
AC200V / 1A, AC240V / 0.5A (COS
Φ
= 0.35) 100,000 times or more
DC24V / 1A, DC100V / 0.1A (L / R = 7
㎳
) 100,000 times or more
Response
time
Off
→
On
10ms or less
On
→
Off
12ms or less
Summary of Contents for XBC-DN10E
Page 1: ......
Page 10: ...Table of Contents Table of Contents 6 10 10 CLEAR ALL PLC 29...