Chapter 6 Instruction Details
XBC E-Type Main Unit
6-66
Ver. 1
(6) If Reset Instruction is used to reset Timer, be sure to input in the same format as used in Timer format shown
below;
A. If TON T0001[Z000] D00010[Z003] is used, Timer format used in reset coil should be T0001[Z000], or
program error will occur in XG5000.
(7) Timer updates present value and contact ON/OFF after END Instruction executed. Thus, Timer Instruction
may make operational error. Refer to Appendix 2. Measurement and Precision of Timer for details.
Reset if used should be the same as the
type of timer used
T0001 D00010
[Z000] [Z003]
M00020
TON
T0001
[Z000]
0
10
D00100.4
( )
T0001
[Z000]
R
ADDP D00100 1 D00100
4
END
13
Index Range
(Z0~Z3)
Remark
1) Due to index function, timers with different characteristics if operated at same time will be executed
individually to produce abnormal operation. If index function is to be used, pay attention to this.