Input Specifications
Input point
8 point, 1 COM
Insulation method
Photo-coupler insulation
Rated input voltage
DC24V
Rated input current
4mA (point 0-3: 7mA)
Operation voltage range
DC20.4~28.8V (within ripple rate 5%)
On voltage / On current
DC19V or higher / 3mA or higher
Off voltage / Off current
DC6V or lower / 1mA or lower
Input resistance
About 5.6k
Ω (P00-P03: 2.7kΩ)
Response
time
Off
→
On
1/3/5/10/20/70/100ms (set by I/O parameter) default: 3ms
On
→
Off
Insulation
Voltage/Resistance
AC560Vrms / 3 cycle (altitude 2000m); 10M
Ω or higher
Output Specifications
Output point
6 point
Insulation method
Photo-coupler insulation
Rated load
voltage/current
DC12-24V; 0.5A per point, 2A per COM, 2 COM (Isolated)
Load Voltage Range
DC10.2 – 26.4V
Off leakage current
0.1mA or less
Max. inrush current
4A/10ms or less
Max. voltage drop when on
DC 0.4V or less
Surge absorber
Zener diode
Photocoupler
(P) Input
Voltage
DC12/24±10% (Ripple voltage 4 Vp-p or less)
Current
6mA
Response time
Off
→
On
1ms or less
On
→
Off
1ms or less (rated load, resistive load)