Chapter 7 Built-in High-speed Counter Function
XBC E-Type Main Unit
7-4
Ver. 1
2. Interface with external devices
a. “E” type
I/O
Internal circuit
Terminal
No.
Signal
Oper
at
ion
On/Off
guaranteed
voltage
1-phase
2-phase
Input
P00
Ch 0
Pulse input
Ch 0
A-phase input
On 20.4~28.8V
Off
6V or less
P01
Ch 1
Pulse input
Ch 0
B-phase input
On 20.4~28.8V
Off
6V or less
P02
Ch 2
Pulse input
Ch 2
A-phase input
On 20.4~28.8V
Off
6V or less
P03
Ch 3
Pulse input
Ch 2
B-phase input
On 20.4~28.8V
Off
6V or less
P04
Ch 0
Preset input
Ch 0
Preset input
On 20.4~28.8V
Off
6V or less
P05
Ch 1
Preset input
-
On 20.4~28.8V
Off
6V or less
P06
Ch 2
Preset input
Ch 2
Preset input
On 20.4~28.8V
Off
6V or less
P07
Ch 3
Preset input
-
On 20.4~28.8V
Off
6V or less
COM0
COM (input common)
2.7 k
Ω
2.7 k
Ω
2.7 k
Ω
2.7 k
Ω
5.6 k
Ω
5.6 k
Ω
5.6 k
Ω
5.6 k
Ω
For XBC-DR10E, there is no physical circuit for P0006 ~ P0007. Turn on this
contact point with program.