![LS Industrial Systems XBC-DN10E User Manual Download Page 518](http://html1.mh-extra.com/html/ls-industrial-systems/xbc-dn10e/xbc-dn10e_user-manual_1943831518.webp)
Chapter 10 Maintenance
XBC E-Type Main Unit
10-16
Ver. 1
Error
code
Error cause
Action
(restart mode after taking an action)
Operation
status
LED
status
Diagnosis
point
500
Data memory backup
error
Check battery, if good, cycle power.
Remote mode is switched to STOP mode.
Warning
1 second
Blink
At Reset
501
Incorrect clock data
Set PLC time with programming software
Warning
0.1 second
Blink
During
Operation
502
Low battery voltage
Remove input power and replace battery
Warning
0.1 second
Blink
During
operation