![LS Industrial Systems XBC-DN10E User Manual Download Page 160](http://html1.mh-extra.com/html/ls-industrial-systems/xbc-dn10e/xbc-dn10e_user-manual_1943831160.webp)
Chapter 6 Instruction Details
XBC E-Type Main Unit
6-43
Ver. 1
6.10 Union Instruction
6.10.1 AND LOAD
Instruction
Area Available
Step
Flag
P M K F L T C S Z D.x R.x
Co
nst.
U N D R
Error
(F110)
Zero
(F111)
Carry
(F112)
AND LOAD
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
-
-
-
1) Function
(1) It performs AND Operation of A Block and B Block.
(2) If AND LOAD is continuously used, normal operation is not available when the maximum usable number is
exceeded.
(3) Up to 15 times (16 blocks) available if continuously used.
2) Program Example
(1) Where Input Condition P00020, P00024 or P00020, P00025 or P00022, P00026 is On, P00060 is Output.
[Ladder Program] [Mnemonic Program]
[Time Chart]
AND LOAD
0
P00020
P00021
P00022
P00025
P00026
P00024
P00023
P00060
ON
ON
OFF
OFF
OFF
OFF
ON
ON
P00020
P00026
P00022
P00060
AND LOAD
A Block
B Block
Step
Mnemonic Operand
0
LOAD
P00020
1
OR NOT
P00021
2
OR
P00022
3
LOAD NOT P00023
4
AND
P00024
5
OR
P00025
6
AND LOAD
7
AND NOT
P00026
8
OUT
P00060