8 Operation
94
8.5.1
Automatic control mode
The automatic control mode is the normal operating mode used by the controller
to
maintain the actual value of a process variable at the specified setpoint. The
controller evaluates the control deviation and controls the output such that the
actual value of the process approaches the setpoint. Changes to the current set-
point can be made in the controller operation screen or in the "parameteriza-
tion". Two setpoints are stored for each controller in the parameterization.
Setpoint 1 is active by default. Setpoint 2 can be activated instead of Setpoint 1
in each controller by means of "Setpoint selection". Setpoints can also be spec-
ified by external sources and transmitted to the controllers in the JUMO AQUIS
touch S via analog inputs. "Setpoint selection" and the configuration of external
setpoints are set in the "Setpoint configuration".
v
Chapter 9.3 "Setpoint values", Page 113
v
Summary of Contents for AQUIS touch P 202580
Page 12: ...Content...
Page 26: ...4 Identifying the device version 26...
Page 29: ...29 5 Mounting Mounting depth with Ci conductivity sensor 283 3 mm 2 3 mm 36 mm 25 mm 23 2 mm...
Page 32: ...5 Mounting 32...
Page 64: ...7 Startup 64...
Page 100: ...1 2 3 4 5...
Page 107: ...107 8 Operation Example of a Quad View...
Page 108: ...8 Operation 108...
Page 114: ...9 Parameterization 114...
Page 160: ...10 Configuration 160...
Page 182: ...13 Calibrating a pH measuring chain 182...
Page 196: ...16 Calibrating CR conductivity sensors 196...
Page 206: ...17 Calibrating Ci conductivity sensors 206...
Page 214: ...18 Calibrating universal inputs 214...
Page 228: ...19 PC Setup Program 228...
Page 319: ...319 20 Technical data...
Page 320: ...20 Technical data 320...
Page 321: ......