10 Configuration
136
Response at hold
inactive
active
hold
Specification of the alarm state when the hold
function is activated, at calibration of the particu-
lar input or at error (overrange/underrange)
inactive:
alarm suppressed
active:
alarm forced
hold:
alarm state is maintained regardless of
alarm condition changes
normal:
alarm in acc. with alarm condition
Response at
calibration
inactive
active
hold
normal
Response at error
inactive
active
hold
Alarm type
inactive
minimum alarm
maximum alarm
alarm window
invert alarm window
Four alarm types (comparator functions) can be
selected to monitor measured values for violation
of limit values.
v
Characteristic lines after the table
only for
CR analysis inputs:
USP
Pre-alarm USP
purified water
Pre-alarm pur. water
Limit value alarms to USP <645> or
European Pharmacopoeia (Ph. Eur.) for
cleaned water
Alarm/Event list
off
event
alarm
Assignment of alarm notification to alarm list or
event list
Alarm text
up to 21 text characters
Text for the alarm/event list
Limit value
-99999 to +99999
Limit value for the particular alarm type
Hysteresis
0 to 99999
Spacing between switch-on and switch-off points
for the alarm types
v
Characteristic lines after the table
Window range
0 to 99999
Range of the alarm window
v
Characteristic lines after the table
Pulse function
Yes
No
Time limit for alarm with the wiper time as maxi-
mum alarm duration
Pulse time
0 to 999 s
Duration of alarm with pulse function activated
Alarm delay
On
0 to 999 s
Time delay between occurrence of the alarm
condition and triggering of the alarm
Alarm delay Off
0 to 999 s
Time delay between ending of the alarm condi-
tion and clearing of the alarm
Configuration point Selection/
setting option
Explanation
Summary of Contents for AQUIS touch P 202580
Page 12: ...Content...
Page 26: ...4 Identifying the device version 26...
Page 29: ...29 5 Mounting Mounting depth with Ci conductivity sensor 283 3 mm 2 3 mm 36 mm 25 mm 23 2 mm...
Page 32: ...5 Mounting 32...
Page 64: ...7 Startup 64...
Page 100: ...1 2 3 4 5...
Page 107: ...107 8 Operation Example of a Quad View...
Page 108: ...8 Operation 108...
Page 114: ...9 Parameterization 114...
Page 160: ...10 Configuration 160...
Page 182: ...13 Calibrating a pH measuring chain 182...
Page 196: ...16 Calibrating CR conductivity sensors 196...
Page 206: ...17 Calibrating Ci conductivity sensors 206...
Page 214: ...18 Calibrating universal inputs 214...
Page 228: ...19 PC Setup Program 228...
Page 319: ...319 20 Technical data...
Page 320: ...20 Technical data 320...
Page 321: ......