10 Configuration
144
10.11.2
Controller inputs
Open:
Device menu
r
Configuration
r
Controller
r
Controller 1 to 4
r
Input
Configuration point Selection/
setting option
Explanation
Description
up to 15 text characters
Designation of the controller input
Actual value
Selection from
Analog selector
Selection of the analog signal source for the ac-
tual value
Output level feedback Selection from
Analog selector
only for modulating controllers and continu-
ous controllers with position feedback:
Selection of the analog signal source for the cur-
rent output level (e.g. universal input with resis-
tance potentiometer or analog input with
standard signal)
Output level feedback is required on continuous
controllers with position feedback.
Parameter selection
Selection from
binary selector
Selection of the digital signal source for switching
from parameter set 1 to parameter set 2
Two parameter sets are stored for each control-
ler and can be switched via this
digital signal.
v
Chapter 9.2 "Parameter Sets (Controller pa-
Digital signal for man-
ual
Selection from
binary selector
Selection of the digital signal source to switch the
controller to manual mode
In addition to the button on the
respective controller screen, it is also
possible to activate manual mode with a
digital signal (e.g. key switch for a digital input)
binary signal (e.g. key switch)
Digital signal for hold Selection from
binary selector
Selection of the digital signal source to switch the
controller to hold mode
Manual text
up to 15 text characters
Text for the alarm/event list upon activation of
manual mode
Alarm text
up to 15 text characters
Text for the alarm/event list upon occurrence of a
dosing alarm
Summary of Contents for AQUIS touch P 202580
Page 12: ...Content...
Page 26: ...4 Identifying the device version 26...
Page 29: ...29 5 Mounting Mounting depth with Ci conductivity sensor 283 3 mm 2 3 mm 36 mm 25 mm 23 2 mm...
Page 32: ...5 Mounting 32...
Page 64: ...7 Startup 64...
Page 100: ...1 2 3 4 5...
Page 107: ...107 8 Operation Example of a Quad View...
Page 108: ...8 Operation 108...
Page 114: ...9 Parameterization 114...
Page 160: ...10 Configuration 160...
Page 182: ...13 Calibrating a pH measuring chain 182...
Page 196: ...16 Calibrating CR conductivity sensors 196...
Page 206: ...17 Calibrating Ci conductivity sensors 206...
Page 214: ...18 Calibrating universal inputs 214...
Page 228: ...19 PC Setup Program 228...
Page 319: ...319 20 Technical data...
Page 320: ...20 Technical data 320...
Page 321: ......