The User Manual of JAC200 Series General Frequency Converter
- 33 -
Function
code
Name
Set range
Default
value
Chan
ge
F6-10
The shutdown mode
0: Deceleration stop
1: Free stop
0
☆
F6-11
The start frequency
of DC braking for
shutdown
0.00 Hz ~ Maximum frequency
0.00Hz
☆
F6-12
The waiting time of
DC braking for
shutdown
0.0s
~
100.0s
0.0s
☆
F6-13
The current of DC
braking for shutdown
0%
~
100%
0%
☆
F6-14
The time of DC
braking for shutdown
0.0s
~
100.0s
0.0s
☆
F6-15
The usage rate for
braking
0%
~
100%
100%
☆
Group F7 The keyboard and display
F7-01
Function Selection of
key M
0: M is invalid
1: The switching of operation panel
command
channel
and
remote
command channel (Terminal command
channel or communications command
channel)
2: The switching of forward running and
reverse running
3: Jog of forward running
4: Jog of reverse running
0
★
F7-02
The function of key
STOP/RESET
0: Only in the keyboard operation mode,
the
shutdown
function
of
key
STOP/RES is valid.
1: The shutdown function of key
STOP/RES is valid in any operation
mode.
1
☆
F7-03
The running display
parameter 1 of LED
0000
~
FFFF
Bit00: Operation frequency 1 (Hz)
Bit01: Set frequency (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: The input state of DI
Bit08: The ouput state of DO
Bit09: AI voltage (V)
Bit10: Reserved
1F
☆