The User Manual of JAC200 Series General Frequency Converter
- 44 -
Function
code
Name
Set range
Default
value
Chan
ge
F9-49
Selection 3 of failure
protection action
Ones place: user-defined
failure (27)
0: Free stop
1: Shut down according to shutdown modes
2: Continue to run
Tens place: user-defined
failure (28)
0: Free stop
1: Shut down according to shutdown modes
2: Continue to run
Hundreds place: The arriving of the
power-on time(29)
0: Free stop
1: Shut down according to shutdown modes
2: Continue to run
Thousand's place: Off load (30)
0: Free stop
1: Deceleration stop
2: Directly jump to the 7% of motor rated
frequency to continue running, at the time
of no off load automatically recover to the
set frequency to run.
Myriabit: PID feedback is missing(31) at
the time of running
0: Free stop
1: Shut down according to shutdown modes
2: Continue to run
00000
☆
F9-50
Selection 4 of failure
protection action
Ones place: Speed deviation is too large
(42)
0: Free stop
1: Shut down according to shutdown modes
2: Continue to run
Tens place: Motor superspeed (43)
Hundreds place: Reserved
00000
☆
F9-54
When failures occur,
it continues to run.
The frequency
selection
0: Run at the current operating frequency
1: Run at the set frequency
2: Run at the upper limitingfrequency
3: Run at the lower limit frequency
4: Run at the abnormal standby frequency
0
☆
F9-55
Abnormal standby
frequency
0.0%
~
100.0%
(100.0% corresponds to the maximum
frequency F0-10)
100.0%
☆
F9-59
The action selection
for instantaneous
power failure
0: Invalid
1: Slow down
2: Deceleration stop
0
☆
F9-60
Judge the voltage
80.0%
~
100.0%
90.0%
☆