The User Manual of JAC200 Series General Frequency Converter
- 30 -
Function
code
Name
Set range
Default
value
Chan
ge
F4-38
The valid mode
selection 1 of DI
terminal
0: High electrical level is valid
1: Low electrical level is valid
Ones place: DI1
Tens place: DI2
Hundreds place: DI3
Thousands place: DI4
Myriabit: Reserved
00000
★
Group F5 Output terminals
F5-02
The function
selection of relay
on the control panel
(T/A-T/C)
0: No output
1: During the operation of frequency
converter
2: Failure output (Be the failure of free
stop )
3: The FDT1 output of detection for
frequency levels
4: The arriving of frequency
5: During the zero speed operation
6:
The pre-alarm for the overload of motor
7: The pre-alarm for the overload of
frequency converter
8: The arriving of the set count value
9:The arriving of the Assigned count value
10: The arriving of length
11: The finish of PLC cycle
12:The arriving of accumulative run time
13: In the frequency limit
14: In the torque limit
15: Ready to run
16:
Reserved
17: The arriving of the upper limiting
frequency
18: The arriving of the upper limiting
frequency (relating to the operation)
19: The output in undervoltage condition
20: Communication reference
21: Finish positioning (reserved)
22: Close to positioning (reserved)
23: In the operation of the zero speed
(output at the time of shutdown)
24: The arriving of accumulative power-on
time
25: The FDT2 output of detection for
frequency levels
26: The arriving output of frequency 1
27: The arriving output of frequency 2
2
F5-04
The selection of DO
output function
1
☆