F4-11
Terminal command mode
3
Three-line type 2
F4-00
Function selection of terminal
DI1
1
Operation-enabled
F4-01
Function selection of terminal
DI2
2
Forward and reverse
running directions
F4-02
Function selection of terminal
DI3
3
Three-line operation
control
Fig. 6-9 Three-line control mode 2
As shown above, in this control mode, when button SB1 is closed and button SB2 is pressed, the frequency
converter runs forward with K disconnected and runs reversely with K closed. The frequency converter
stops as soon as button SB1 is disconnected. In the normal start and operation, button SB1 must be kept
closed, while the commands of button SB2 take effect as soon as it is closed.
F4-12
UP/DOWN change rate of the
terminal
Default value
1.00Hz/s
Set range
0.01Hz/s
~
65.535Hz/s
It is used to set the frequency change rate, namely, the frequency variation per second, when the set
frequency of terminal UP/DOWN is adjusted.
When F0-22(decimal places of frequency) is 2, the range of this value is 0.001Hz/s ~65.535Hz/s.
When F0-22(decimal places of frequency) is 1, the range of this value is 0.01Hz/s ~655.35Hz/s.
F4-13
A1 curve 1 minimum input
Default value
0.00V
Set range
0.00V
~
F4-15
F4-14
A1 curve 1 corresponding setting
of minimum input
Default value
0.0%
Set range
-100.00%
~
100.0%
F4-15
A1 curve 1 maximum input
Default value
10.00V
Set range
F4-13
~
10.00V
F4-16
A1 curve 1 corresponding setting
Default value
100.0%