The User Manual of JAC200 Series General Frequency Converter
- 22 -
Function
code
Name
Set range
Default
value
Chan
ge
F0-24
Selection of motor
parameter set
0: Motor parameter set 1
1: Motor parameter set 2
0
★
F0-25
Reference frequency
of
cceleration/decelerati
on time
0: Maximum frequency (F0-10)
1: Set frequency
2
:
100Hz
0
★
F0-26
Frequency
instruction
UP/DOWN standard
in running
0: Operation frequency 1: Set frequency
0
★
F0-27
Command source
binding frequency
source
Ones place: Operation panel command
binding frequency source selection
0: No binding
1: Digital setting frequency
2: AI
3:
Reserved
4: Key
potentiometer
5: Reserved
6: Multi-speed
7: Simple PLC
8: PID
9: Communication reference
Tens place: Terminal command binding
frequency source selection
Hundreds place: Communication command
binding frequency source selection
Thousands
place:
Automatic
running
binding frequency source selection
0000
☆
F1 The first motor group
F1-00
Selection of motor
type
0: Ordinary asynchronous motor
1: Variable frequency asynchronous motor
0
★
F1-01
Rated power of
motor
0.1kW
~
400.0kW
Model
dependent
★
F1-02
Rated voltage of
motor
1V
~
2000V
Model
dependent
★
F1-03
Rated current of
motor
0.01A~655.35A (Power of frequency
converter <=55kW)
0.1A~6553.5A
(Power
of
frequency
converter >55kW)
Model
dependent
★
F1-04
Rated frequency of
0.01Hz
~
maximum frequency
Model
★