The User Manual of JAC200 Series General Frequency Converter
- 115 -
Fig. 6-20 Arbitrarily arriving frequency test diagram
F8-34
Zero current test level
Default value
5.0%
Set range
0.0%
~
300.0% (Rated current of motor)
F8-35
Lagged test time of zero current
Default value
0.10s
Set range
0.00s
~
600.00s
When the output current of the frequency converter is less than or equal to zero current test level, and the
duration exceeds the lagged test time of zero current, the multifunctional DO of the frequency converter
shall output ON signal. Fig. 6-21 is the zero current test diagram.
Fig. 6-21 Zero current test diagram
F8-36
Output current over limit value
Default value
200.0%
Set range
0.0% (Not detected); 0.1%
~
300.0% (Rated current
of motor)
F8-37
Delay time of over limit test for
output current
Default value
0.00s
Set range
0.00s
~
600.00s
When the output current of the frequency converter is greater than or exceeds test point limit, and the