The User Manual of JAC200 Series General Frequency Converter
- 97 -
2
Output current
0
~
2 times rated current of motor
3
Output torque (absolute
value)
0
~
2 times rated torque of motor
4
Output power
0
~
2 times rated power
5
Output voltage
0
~
1.2 times rated voltage of frequency converter
6
Resrved
Reserved
7
AI
0V
~
10V
8
Resrved
Reserved
9
Key
potentiometer
0V
~
10V
10
Length
0
~
Maximum set length
11
Count value
0
~
Maximum count value
12
Communication reference
0.0%
~
100.0%
13
Motor speed
0
~
Speed corresponding to maximum output frequency
14
Output current
0.0A
~
1000.0A
15
Output voltage
0.0V
~
1000.0V
16
Output torque (practical
value)
-2 times rated torque of motor
~
2 times rated torque of
motor
17
Outpput frequency
converter
the actual value of torque
F5-10
A O zero bias coefficient
Default value
0.0%
Set range
-100.0%
~
+100.0%
F5-11
AO gain
Default value
1.00
Set range
-10.00
~
+10.00
Generally, above function codes are used to correct the zero drift of analog output and deviation of output
amplitude and also can be used to define the AO output curve required.
If zero bias is expressed as “b”, gain is expressed as k, practical output is expressed as Y and standard
output is expressed as X, then practical output can be calculated by the equation: Y=kX
+
b
Where, the zero bias coefficients of AO are 100% corresponding to 10V . Standard output means the
quantity expressed by analog output corresponding to output 0V
~
10V.
For example: If the analog output is operation frequency, gain shall be set as “-0.50” and zero bias shall be
set as “80%” to ensure that the output shall be 8V when frequency is 0 and the output shall be 3V when
frequency is the maximum frequency.
F5-18
RELAY output delay
Default value
0.0s
Set range
0.0s
~
3600.0s
F5-20
DO output delay
Default value
0.0s