The User Manual of JAC200 Series General Frequency Converter
- 24 -
Function
code
Name
Set range
Default
value
Chan
ge
F2-05
Switching Frequency
2
F2-02 ~maximum frequency
10.00Hz
☆
F2-06
Slip gain of vector
control
50%
~
200%
100%
☆
F2-07
Filtering time
constant of speed
loop
0.000s
~
0.100s
0.050s
☆
F2-09
Upper limiting
source of torque in
speed control mode
0: Function code F2-10 setting
1: AI
2:
Reserved
3: Key
potentiometer
4: Reserved
5: Communication reference
6:
Reserved
7:
Reserved
The full range of Option 1-7 corresponds to
F2-10
0
☆
F2-10
Digital setting of
upper limiting torque
in speed control
mode
0.0%
~
200.0%
150.0%
☆
F2-13
Proportional gain of
excitation regulation
0
~
60000
2000
☆
F2-14
Integral gain of
excitation regulation
0
~
60000
1300
☆
F2-15
Proportional gain of
torque regulation
0
~
60000
2000
☆
F2-16
Integral gain of
torque regulation
0
~
60000
1300
☆
F2-20
Maximum flux
weakening current
100%
~
110%
105%
☆
F2-21
Automatic regulation
gain of flux
weakening
50%
~
200%
100%
☆
F3 V/F control parameters