The User Manual of JAC200 Series General Frequency Converter
- 71 -
Set range
0.01A
~
655.35A(frequency converter power<=55kW)
0.1A
~
6553.5A(frequency converter power >55kW)
F1-04
Rated frequency
Default value
Model dependent
Set range
0.01Hz-maximum frequency
F1-05
Rated speed
Default value
Model dependent
Set range
1rpm
~
65535rpm
Above function code is motor nameplate parameter. Whatever you choose VF control or vector control you
both need set relevant parameter according to motor nameplate.
For getting better VF or vector control performance, we need adjust motor parameter, and the accuracy of
adjusting result is related with setting correctly motor nameplate parameter.
F1-06
Stator resistance of
asynchronous motor
Default value
Model dependent
Set range
0.001Ω -65.535Ω( the power of frequency
converter≤55kW)
0.0001Ω -6.5535Ω(the power of frequency
converter >55kW)
F1-07
Rotor resistance of
asynchronous motor
Default value
Model dependent
Set range
0.001Ω -65.535Ω(the power of frequency
converter≤55kW)
0.0001Ω -6.5535Ω(the power of frequency
converter >55kW)
F1-08
Leakage inductive
reactance of asynchronous
motor
Default value
Model dependent
Set range
0.01mH -655.35mH(the power of frequency converter
≤55kW)
0.001mH-65.535mH(the power of frequency
converter >55kW)
F1-09
Interaction inductive
reactance of asynchronous
motor
Default value
Model dependent
Set range
0.1mH -6553.5mH(the power of frequency converter
≤55kW)
0.01mH -655.35mH(the power of frequency
converter >55kW)
F1-10
No-load current of
asynchronous motor
Default value
Model dependent