Set range
0.01A -F1-03(the power of frequency converter ≤55kW)
0.1A-F1-03(the power of frequency converter >55kW)
F1-06-F1-10 is the parameter of asynchronous motor. The motor nameplate usually doesn’t have these
parameters. You can get them through the self-tuning of frequency converter. Where, “static tuning of
asynchronous motor” only can get three parameters from F1-06 to F1-08, and but “complete tuning of
asynchronous motor” not only can get 5 parameters in here, also can get phase sequence of encoder,
parameter PI of current loop etc.
When change motor rated power (F1-01) or motor rated voltage (F1-02), the frequency converter will
modify the value from F1-06-F1-10 and restore 5 parameters to the common standard Y serial motor
parameter.
If you can not tune for asynchronous motor at field, you can input above corresponding function code
according to the parameter provided by manufacturers.
F1-37
Tuning selection
Default value
0
Set range
0
No-operation
1
Static tuning for asynchronous motor
2
Complete tuning for asynchronous motor
3
Static and complete parameter identification
0: No-operation means forbid to tune.
1: Static tuning for asynchronous motor is suitable for that kind of condition that asynchronous motor is not
easy to separate with load, but can not do complete tuning.
Before static tuning for asynchronous motor, have to set motor type and motor nameplate parameter from
F1-00 to F1-05. For the static tuning of asynchronous motor, frequency converter can get 3 parameters from
F1-06 to F1-08.
Description of the operation: set this function code as 1, then press RUN key, and the frequency converter
shall do static tuning.
2: complete tuning for asynchronous motor.
For ensuring the dynamic control performance, please choose the complete tuning. At this time motor have
to separate with load to keep the motor is in no-load state.
Frequency converter do the static tuning first, then accelerate to 80% of motor rated frequency as
acceleration time F0-17 and keep it for some time and do deceleration stop as deceleration time F0-18 and
at last finishing tuning during the process of complete tuning.
Before doing the complete tuning of asynchronous motor, except for need set motor type and motor
nameplate parameters from F1-00 to F1-05.
For complete tuning of asynchronous motor, frequency converter can get 5 motor parameters from F1-06 to
F1-10 and AB phase sequence F1-30 of encoder, current loop with vector control PI parameters from F2-13