The User Manual of JAC200 Series General Frequency Converter
- 45 -
Function
code
Name
Set range
Default
value
Chan
ge
when instantaneous
action stops
F9-61
Judge the time when
the voltage recovers
during instantaneous
power failure
0.00s
~
100.00s
0.50s
☆
F9-62
Judge the voltage in
the instantaneous
power failure action
60.0%
~
100.0% (Standard Bus voltage)
80.0%
☆
F9-63
Protection
selection of off load
0: Invalid
1: Valid
0
☆
F9-64
Detection level
of off load
0.0
~
100.0
%
10.0%
☆
F9-65
Detection time of off
load
0.0
~
60.0s
1.0s
☆
F9-67
Detection value of
overspeed
0.0
%~
50.0
%
(Maximum frequency)
20.0%
☆
F9-68
Detection time of
overspeed
0.0s: No detection
0.1
~
60.0s
1.0s
☆
F9-69
The detection value
of too large speed
deviation
0.0
%~
50.0
%
(Maximum frequency)
20.0%
☆
F9-70
The detection time
of too large speed
deviation
0.0s: No detection
0.1
~
60.0s
5.0s
☆
Group FA PID function
FA-00
PID Given source
0: FA-01 setting
1: AI
2: Reserved
3: Key
potentiometer
4: Reserved
5:
Communication reference
6: Multi-stage instructions reference
0
☆
FA-01
PID value reference
0.0%
~
100.0%
50.0%
☆